Term
| List the Generator Field breaker trips |
|
Definition
|
|
Term
| Function of the main generator |
|
Definition
| Convert mechanical energy of shaft rotation into electrical energy, which is distributed over the power grid. |
|
|
Term
| Power supply to Isophase Bus Cooler Blower Motor |
|
Definition
|
|
Term
| With what two conditions should the isophase bus blower NOT be placed in service? |
|
Definition
| Outside air temperature less than 32 degrees F. AND Generator not on line. |
|
|
Term
| Operating limit below which isophase bus is capable of self-cooling? |
|
Definition
Main generator less than 10,500 amps (approx 400 MWe) |
|
|
Term
| Should one of the hydrogen coolers fail, it may be removed from service for an indefinite period of time provided… |
|
Definition
| Generator load does not exceed 531 MWe at a power factor of 1.00 with hydrogen pressure 43 to 45 psig. |
|
|
Term
| Minimum seal oil pressure when operating |
|
Definition
| 3 psig above hydrogen pressure in generator casing |
|
|
Term
| Minimum seal oil pressure at a standstill |
|
Definition
| 1 psig above hydrogen pressure in generator casing |
|
|
Term
| Max differential pressure between seal oil and hydrogen pressure |
|
Definition
|
|
Term
| Hydrogen purity that should preferably not be allowed to fall below |
|
Definition
| 90% (Upper explosive limit is 75%) |
|
|
Term
| Generator gas pressure at rated conditions |
|
Definition
|
|
Term
| Power supply to Generator Hydrogen control panel |
|
Definition
|
|